Online UPS
MF Series
1-phase input – 1-phase output1 kVA – 3 kVA
The MF Series (1–3 kVA) is a single-phase input, single-phase output online UPS family with a pure sine wave output and advanced communication options.
Using high-frequency true double conversion, the MF Series protects medical systems such as laboratory analysers, operating theatres and ultrasound devices, as well as security systems, automation, computer networks and communication systems against power cuts and energy fluctuations.
- Uninterrupted, stable power
- High protection for critical loads
- Continuous sine wave output
Product Features
- High-frequency true double conversion
- DSP (Digital Signal Processor) technology
- Input power factor correction (PFC)
- Wide input voltage range (110~300 V)
- Remaining battery runtime display
- LED indicator that changes colour with the operating mode
- Output power factor = 0.9
- Cold start (start from battery without mains)
- Automatic frequency detection
- Frequency converter mode
- ECO mode for high energy savings
- Output voltage selectable on the LCD display
- Self-test at start-up
- Advanced battery management (ABM)
- Short-circuit and overload protection
- Automatic battery charging while switched off
- Load-sensing intelligent fan control
- Excellent generator compatibility
- Standard RS232 / USB
- Standard emergency power off function (EPO)
- SNMP / AS400 / Modbus (optional)
- Expandable battery unit with an additional charger card (optional)
- Parallel operation of up to 3 units (optional)
- Electromagnetic compatibility, EMC – LVD CE certificates
- 2-year warranty / 10-year spare parts warranty
| MODEL | MF-1 | MF-2 | MF-3 |
|---|---|---|---|
| POWER | 1.000 VA / 900 W | 2.000 VA / 1.800 W | 3.000 VA / 2.700 W |
| MODEL | MF-1 | MF-2 | MF-3 |
|---|---|---|---|
| Voltage | 208 / 220 / 230 / 240 Vac. | ||
| Voltage range | At 100% load: 176 ~ 300 Vac / at 50% load: 110 ~ 300 Vac | ||
| Frequency | 45 ~ 55 Hz /54 ~ 66 Hz. | ||
| Input power factor | ≥ 0,98 | ||
| MODEL | MF-1 | MF-2 | MF-3 |
|---|---|---|---|
| Voltage | 200 / 208 / 220 / 230 / 240 Vac – selectable on the LCD panel (10% power derating at 200/208 Vac) | ||
| Voltage regulation | ± %1 | ||
| Frequency | 50 / 60 Hz ±0.05 Hz | ||
| Waveform / output power factor | Pure sine wave / 0.9 | ||
| Crest factor | 3:1 | ||
| Harmonic distortion | ≤ 2% with linear load; ≤ 5% with non-linear load | ||
| Overload capacity | 100–105%: continuous / 105–130%: 60 s / 130–150%: 10 s / 150%: 300 ms | ||
| Transfer time | Battery–inverter = 0 ms / inverter–bypass = 4 ms / ECO mode–battery mode = 10 ms | ||
| Battery mode to inverter mode | 0 ms | ||
| Inverter mode to bypass mode | <4 ms | ||
| ECO mode to battery mode | <10 ms | ||
| Number of output terminals | 3 sockets | 4 sockets | 4 sockets |
| MODEL | MF-1 | MF-2 | MF-3 |
|---|---|---|---|
| Mains operation | ≥ %89 | ≥ %90 | ≥ %91 |
| MODEL | MF-1 | MF-2 | MF-3 |
|---|---|---|---|
| Battery voltage | 24 Vdc. (Std) | 48 Vdc. (Std) | 72 Vdc. (Std) |
| Battery count / model | 2*7 / 9 Ah. | 4*7 / 9 Ah. | 6*7 / 9 Ah. |
| Battery charging current (standard model) | 1 Amp. | ||
| Battery charging current (long-backup L model) | 6 Amp. | ||
| Battery charging time | 90% capacity in 5 hours | ||
| MODEL | MF-1 | MF-2 | MF-3 |
|---|---|---|---|
| Mains failure | AUDIBLE / LED ALARM | ||
| Low battery | |||
| Overload | |||
| General UPS fault | |||
| MODEL | MF-1 | MF-2 | MF-3 |
|---|---|---|---|
| Display | Segment LCD | ||
| RS232 | YES | ||
| USB | YES | ||
| EPO | YES | ||
| Communication slot | YES / SNMP – Modbus – AS400 card optional | ||
| SNMP | Optional | ||
Other Online UPS Series
Frequently Asked Questions
What should I consider when choosing a UPS?
The power of the load to be protected (VA/W), the required backup time, the input and output phase configuration, the installation environment and communication needs are assessed together. If you share your load details, we can help you choose the right model.
Which applications is the MF Series suitable for?
The MF Series (1–3 kVA) is a single-phase input, single-phase output online UPS family with a pure sine wave output and advanced communication options.
Is there technical documentation for the MF Series?
Yes. You can reach the product's technical specifications from the catalogue (PDF) on this page. The technical specifications table is also on the page.
How long is the warranty?
2-year warranty / 10-year spare parts warranty.